60 Implementation plan Project Details Where- All our 3 plants in Gotan i.e. JK White, JK cement(Grey), Thermal power plant When - 2018-19 Who - E & I Team How - Implementation plan Technical Details Meter Communication Software - SCADA- PSE 8.2 Mode of Communication- RS485 & Ethernet Devices used for communication- Ethernet Switch- EGX 100, Media Convertor Types of Meters configured- PM500, PM820, PM5330, EM6400NG, EM6436, ION 7650 All the meters whose consumption was to be monitored and captured were Connected through Modbus communication. Energy meters away from server More than 100meters, were connected through 6 Nos. of I/O panels(JKWC,TPP, JKC) which were connected to server through Optical Fibre cable. Total No. of meters communicated – 267Nos SR. NO. 1 2 3 4 5 6 7 ACTION PLAN Identi cation of requirement Approval frommanagement & third party qoutation nalisation Procurement, inspection & testing of system Rs-485 communication of meters & di-do wiring Meter con guration in scada & load shedding programming Testing of load shedding system, reports Checking all meters parameters such as trends, values, alarms JAN 18 FEB 18 APRIL 18 MAY 18 JUNE 18 JULY 18